Model: MultiPlus-II 48/5000/70-50 S/N: HQ1920MRH3W Firmware: 2623568 Name: '$7A00906E' TAB: General System frequency 50Hz Shore current 17.0 A Overruled by remote checked Dynamic current limiter checked External current sensor connected (see manual) unchecked State of charge when Bulk finished 85.0 % Battery capacity 683 Ah Charge efficiency 0.80 TAB: Grid Country / grid code standard None: (feeding energy from DC to grid not allowed) Accept wide input frequency range (45-65 Hz) checked AC low switch mains off 180 V AC low switch mains on 187 V AC high switch mains on 265 V AC high switch mains off 270 V UPS function unchecked TAB: Inverter PowerAssist unchecked Inverter output voltage 230 V Ground relay checked Inverter DC shut-down voltage 45.00 V Inverter DC restart voltage 50.00 V Low DC alarm level 46.00 V Do not restart after short-circuit (VDE 2510-2 safety) unchecked enable AES unchecked TAB: Charger Enable charger checked Weak AC input checked Stop after excessive bulk unchecked Lithium batteries unchecked Disable VSense (for diagnostic purposes) unchecked Storage mode checked Use equalization (tubular plate traction battery curve) unchecked Charge curve Adaptive + BatterySafe Absorption voltage 59.20 V Float voltage 52.56 V Charge current 34 A Repeated absorption time 1.00 Hr Repeated absorption interval 7.00 Days Maximum absorption time 5 Hr Temperature compensation -120.0 mV/deg TAB: Virtual switch TAB: Usage Virtual switch usage Do not use VS TAB: Assistants TAB: Assistant Configuration Assistants not used TAB: Advanced limit internal charger to prioritize other energy sources unchecked